Wipro Limited
General Information:
Client: Wipro Limited
City: Kolkata
Climate: Warm & Humid
Operational schedule –24 hours, 6 working days in a week
Area of the building : 11079.2m² (out of which 7621.0 m² - conditioned
area, 3458.2 m² - Non- conditioned area)
Green Building Design Features:
Building Design
Orientation

- Tower 1 & 2: Longer axis N-S
- Tower 3 & Cafeteria: E-W
- Learning Center – N-E
The orientation of Towers 1 & 2 helps in reducing solar heat gains.
Orientation of window openings of Tower 1 & 2 on N-S helps in reducing
cooling loads and reducing the overall air-conditioning requirement
and hence saves energy.
The proper building orientation plays an important role with regard
to solar radiation and wind.
Landscape

The three towers are planned around courtyards which are green spaces
around the building blocks.
Maintains comfortable micro-climate and contribute towards energy conservation.
Trees reduce direct solar heat, provide shade and prevent heating up
of building surfaces and heat island effect.
Also helps in maintaining a lower ambient temperature around the buildings
and hence better microclimate.
Building Envelope
Walls
Walls of air-conditioned zones in all blocks - 230 mm brick with 12.5
mm plaster
Roof

Roof Towers 1,2,3, learning centre, and guest house
Window
6 mm brown single windows
- (SC – 0.52, U-value of Glass – 5.7 W/m2K) WWR – 11.1%
Tinted single glazed window helps in reducing solar heat gain. Optimum
WWR which is less than ECBC standard (40%) helps in reducing external
solar heat gain.

Building Lighting
Day light integration
Due to less window wall ratio, daylight integration has not been the
focus in this building.
Small windows at the seating areas can reduce thermal discomfort.
The reduced percentage of window area to wall area helps in reducing the
external heat gain into the building.
Lighting system
- 6% of the total connected load for the building (273 kW of indoor
lighting, 30 kW of outdoor lighting)
- Luminaires used mostly – one efficient recessed type luminaires
with twin 36 W CFLs
- LPD – 6.9 W/m2
- The LPD (6.9 W/m2) is less than the maximum allowed LPD of ECBC
(10.8 W/m2) which is very good.
- According to Energy Star, CFLs provide the same amount of light
as ordinary bulb using 75% less energy.
- It also generates 75% less heat, reducing cooling costs.
HVAC system Design
Central plant with 4 chillers of 2 types with 1610 TR
cooling capacity
- Screw type chillers
- Centrifugal chillers
Energy Performance of the Building
Lighting Energy Performance of the Building

- Annual consumption (lighting) – 917501 kWh
- Lighting Performance Index – 23 kWh/sq.mt/annum
Space Conditioning Energy Performance of the Building

- Annual consumption (A/C) – 7798385 kWh
- Operating cooling demand – 196 sq.ft/TR
Annual energy consumption due to lighting & air conditioning (kWh):
445335
Energy Performance Index of the building (KWh/sq.mts of built up area/annum):
219
Energy Saving Potential
Impact of Low energy strategies:
 |
| Parameter comparison |
Conventional case |
Existing case (Low energy strategies) |
| Electrical load |
Base case |
6% less than the conventional case |
| Cooling Load |
Base case |
17% less than the conventional case |
| EPI |
Base case |
5% less than the conventional case |
|
Impact of ECBC envelope:
 |
| Parameter comparison |
Conventional case |
Existing case (ECBC envelope) |
| Electrical load |
Base case |
5% less than the conventional case |
| Cooling Load |
Base case |
13% less than the conventional case |
| EPI |
Base case |
5% less than the conventional case |
|
Impact of ECBC recommended LPD:
 |
| Parameter comparison |
Conventional case |
Existing case (ECBC envelope) |
| Electrical load |
Base case |
12% less than the conventional case |
| Cooling Load |
Base case |
9% less than the conventional case |
| EPI |
Base case |
13% less than the conventional case |
|
Impact of ECBC recommended chiller efficiency:
 |
| Parameter comparison |
Conventional case |
Existing case (ECBC envelope) |
| Electrical load |
Base case |
9% less than the conventional case |
| Cooling Load |
Base case |
No change |
| EPI |
Base case |
7% less than the conventional case |
|
Impact of HVAC controls:
 |
| Parameter comparison |
Conventional case |
Existing case (ECBC envelope) |
| Electrical load |
Base case |
16% less than the conventional case |
| Cooling Load |
Base case |
No change |
| EPI |
Base case |
16% less than the conventional case
|
|
Impact of ECBC recommended energy conservation measures:
 |
| Parameter comparison |
Conventional case |
Existing case (ECBC envelope) |
| Electrical load |
Base case |
23% less than the conventional case |
| Cooling Load |
Base case |
23% less than the conventional case |
| EPI |
Base case |
21% less than the conventional case
|
|
Impact of ECBC recommended energy conservation measures:
 |
| Parameter comparison |
Conventional case |
Existing case (ECBC envelope) |
| Electrical load |
Base case |
38% less than the conventional case |
| Cooling Load |
Base case |
30% less than the conventional case |
| EPI |
Base case |
35% less than the conventional case
|
|
Comparison of various parameters for solar passive building (Wipro)
with conventional case:
| Parameters |
Solar passive Case |
Conventional Case |
| Building design |
Building longer facades are 45 degree inclined
to North
No roof and wall shading |
Building orientation was changed to longer
facades facing East-West
No roof and wall shading |
| Building Envelope |
No insulation on wall and roof.
U value for Wall -1.92 W/m2/K
U Value for Roof-2.74 W/m2/K
Single Glazed windows( U value of glass -5.7 W/m2/K and Shading
coefficient-0.52)
|
No insulation on wall and roof.
U value for Wall -1.92 W/m2/K
U Value for Roof-3.35 W/m2/K
Single Glazed windows( U value of glass -6.14 W/m2/K and Shading
coefficient-0.815) |
| Building Lighting Power density |
Lighting power density is 6.9 W/m2 |
Lighting power density changed to 20 W/m2
|
| Building Chiller |
2 water cooled screw type chillers having
a COP 2.6-2.9
2 water cooled Centrifugal water cooled chiller having a COP
4.0-4.3
|
Air cooled screw chillers with COP of 3.2 |
| Energy performance Index (KWh/m2/yr) |
219 |
335 |
|