Climate Zone Moderate
ECBC Complaint Building, WIPRO Info Tech, Bangalore
General Information:
Client: WIPRO Info Tech
City: Bangalore
Climate: Moderate
Operational schedule – 10 hours, 5 working days in a week for 10
floors, 24 hours for 2 floors
Area of the building: 32, 438 m² (out of which 24, 440m² - conditioned
area, 7, 998m² - non-conditioned area)
Green Building Design Features:
Building Design
Orientation
1:3 rectangular with longer façade on N-S and shorter façade on
E-W
|
Building Envelope |
Walls
200mm concrete block with 30mm plaster on exterior
side and 20mm plaster on interior side |
Roof
250mm of RCC concrete slab |
| |
Windows
- Double glazing window (6-12-6)mm
- Glass on north orientation has a lighter light transmission
- The glazing for the building has been designed to maximize
the effect of natural light, largely eliminating the need for
artificial light during day time
- The high performance window glass, while allowing light inside,
does not allow heat and also keeps office cool from inside during
the day decreasing the load on HVAC systems
- Optimum WWR which is less than ECBC standard (40%) helps in
reducing external solar heat gain
|
Building Lighting
Lighting System
- 9.4% of the (273 kW of indoor lighting, 30kW of outdoor lighting)
- Luminaries used mostly –recess mounted direct-indirect down
light luminaries with twin fitting 36 W CFL lamps and low loss
copper ballast
- LPD – 11.2-12.4 W/m2
- The LPD (11.2 W/m2) is less than the max allowed LPD of ECBC
(11.8 W/m2) for office space which is very good.
- According to Energy Star, CFLs provide the same amount of
light as ordinary bulb using 75% less energy.
- It also generates 75% less heat, reducing cooling costs
Lighting Controls
- Occupancy sensors have been integrated with luminaires in
the office space
- Reduce energy by turning the lights on when someone enters
and switches off, when the room is empty
HVAC System Design
|
Energy performance of the building
Lighting Energy Performance of the Building

- Annual Consumption (lighting) – 324754 KWh
- Lighting Performance Index – 13 KWh/Sqmt/annum
Space Conditioning Energy Performance of the Building

- Annual Consumption (A/C) – 24440 KWh
- HVAC Performance Index – 137 KWh/Sqmt/annum
|
Annual energy consumption due to lighting & air conditioning
(kWh): 3448073
Overall Energy Performance Index due to lighting & air conditioning
(kWh/m2): 118 |
|
| |
|
|
Comparison of various parameters
for ECBC compliant Moderate (WIPRO) with conventional case
The table below summarizes the calibrated existing ECBC model case,
conventional case generated over the existing building in moderate
climate zone.
|
|
| Parameters |
ECBC compliant case (Existing Building) features |
Conventional Case (Building features) |
| Building orientation |
Longer façade on N-S and shorter façade
on E-W |
Building orientation to longer facades facing
East-West |
| windows shaded on E-W orientation |
Windows, Walls and Roof are not shaded |
| Building Envelope |
Insulation on roof with air gap for walls
U value for Wall - 1.29 W/m2/K
U Value for Roof - 0.47 W/m2/K
|
No insulation on wall and roof.
U value for Wall -1.94 W/m2/K
U Value for Roof-1.5 W/m2/K
|
Double Glazed windows( U value
of glass -2.64 W/m2/K and Shading coefficient-0.17)
WWR - 26% |
Single Glazed windows( U value
of glass -6.17 W/m2/K and Shading coefficient-0.61)
WWR – 26% |
| Building Lighting Power density |
Lighting power density is 11.8 W/m2 |
Lighting power density 20 W/m2 |
| Controls |
Occupancy sensors |
No controls or sensors |
| Building Chiller |
4 water cooled screw chillers with COP of
6.4 (rated) |
PTAC units having EER of 8.4 and Fan power
as 0.000134 bhp/cfm |
| Energy performance Index (KWh/m2/yr) |
118 |
167 |
Energy Saving Potential
The conventional case defined above was selected to run different
energy saving options and to finally quantify the energy saving
potential which can be realized in moderate climate by incorporating
the low design strategies, ECBC envelope, and the best case (incorporating
both low energy strategies and ECBC measures)
Impact of Low energy strategies
The conventional case was run by incorporating low energy solar
passive design strategies on the annual electricity consumption
(kWh), electric load (kW) and cooling demand (TR) of the building.
 |
| Parameter comparison |
Conventional case |
Existing case Low energy strategies) |
| Electrical load |
Base case |
14.7% less than the conventional case |
| Cooling Load |
Base case |
38.6% less than the conventional case |
| EPI |
Base case |
25.4% less than the conventional case |
|
Impact of ECBC Envelope
The conventional case was run by incorporating ECBC envelope on
the annual electricity consumption (kWh), electric load (kW) and
cooling demand (TR) of the building.
 |
| Parameter comparison |
Conventional case |
Existing case Low energy strategies) |
| Electrical load |
Base case |
14.6% less than the conventional case |
| Cooling Load |
Base case |
13.6% less than the conventional case |
| EPI |
Base case |
12.6% less than the conventional case |
|
Overall Impact of ECBC Envelope and low energy strategies
The conventional case was run by incorporating both the low energy
solar passive design strategies and ECBC envelope on the annual
electricity consumption (kWh), electric load (kW) and cooling demand
(TR) of the building.
 |
| Parameter comparison |
Conventional case |
Existing case Low energy strategies) |
| Electrical load |
Base case |
32.4% less than the conventional case |
| Cooling Load |
Base case |
56.9% less than the conventional case |
| EPI |
Base case |
26.4% less than the conventional case |
|

The above graph shows the variation in the Electrical load (kW),
Coil load (TR) and EPI (energy performance index) for all the cases.
The below table gives the comparison of the impact of ECBC, Low
energy strategies, and ECBC + low energy strategies on conventional
case for WIPRO building for a Moderate Climate
| Parameter comparison |
Existing case |
Conventional case |
ECBC case |
Low energy strategy |
ECBC+Low energy strategy |
| Electrical load |
35% less than the conventional case |
Base case |
14.6% less than the conventional case |
14.7% less than the conventional case |
32.4% less than the conventional case |
| Coil Load |
52% less than the conventional case |
Base case |
13.6% less than the conventional case |
38.6% less than the conventional case |
56.9% less than the convention al case |
| EPI |
28% less than the conventional case |
Base case |
12.6% less than the conventional case |
25.4% less than the conventional vase |
26.9% less than the conventional case |
|
| |
|